Paper |
Title |
Page |
MOPMN027 |
The LHC Sequencer |
300 |
|
- R. Alemany-Fernandez, V. Baggiolini, R. Gorbonosov, D. Khasbulatov, M. Lamont, P. Le Roux, C. Roderick
CERN, Geneva, Switzerland
|
|
|
The Large Hadron Collider (LHC) at CERN is a highly complex system made of many different sub-systems whose operation implies the execution of many tasks with stringent constraints on the order and duration of the execution. To be able to operate such a system in the most efficient and reliable way the operators in the CERN control room use a high level control system: the LHC Sequencer. The LHC Sequencer system is composed of several components, including an Oracle database where operational sequences are configured, a core server that orchestrates the execution of the sequences, and two graphical user interfaces: one for sequence edition, and another for sequence execution. This paper describes the architecture of the LHC Sequencer system, and how the sequences are prepared and used for LHC operation.
|
|
|
Poster MOPMN027 [2.163 MB]
|
|
|
WEPMU011 |
Automatic Injection Quality Checks for the LHC |
1077 |
|
- L.N. Drosdal, B. Goddard, R. Gorbonosov, S. Jackson, D. Jacquet, V. Kain, D. Khasbulatov, M. Misiowiec, J. Wenninger, C. Zamantzas
CERN, Geneva, Switzerland
|
|
|
Twelve injections per beam are required to fill the LHC with the nominal filling scheme. The injected beam needs to fulfill a number of requirements to provide useful physics for the experiments when they take data at collisions later on in the LHC cycle. These requirements are checked by a dedicated software system, called the LHC injection quality check. At each injection, this system receives data about beam characteristics from key equipment in the LHC and analyzes it online to determine the quality of the injected beam after each injection. If the quality is insufficient, the automatic injection process is stopped, and the operator has to take corrective measures. This paper will describe the software architecture of the LHC injection quality check and the interplay with other systems. A set of tools for self-monitoring of the injection quality checks to achieve optimum performance will be discussed as well. Results obtained during the LHC commissioning year 2010 and the LHC run 2011 will finally be presented.
|
|
|
Poster WEPMU011 [0.358 MB]
|
|
|
WEPMU023 |
External Post-Operational Checks for the LHC Beam Dumping System |
1111 |
|
- N. Magnin, V. Baggiolini, E. Carlier, B. Goddard, R. Gorbonosov, D. Khasbulatov, J.A. Uythoven, M. Zerlauth
CERN, Geneva, Switzerland
|
|
|
The LHC Beam Dumping System (LBDS) is a critical part of the LHC machine protection system. After every LHC beam dump action the various signals and transient data recordings of the beam dumping control systems and beam instrumentation measurements are automatically analysed by the eXternal Post-Operational Checks (XPOC) system to verify the correct execution of the dump action and the integrity of the related equipment. This software system complements the LHC machine protection hardware, and has to ascertain that the beam dumping system is ‘as good as new’ before the start of the next operational cycle. This is the only way by which the stringent reliability requirements can be met. The XPOC system has been developed within the framework of the LHC “Post-Mortem” system, allowing highly dependable data acquisition, data archiving, live analysis of acquired data and replay of previously recorded events. It is composed of various analysis modules, each one dedicated to the analysis of measurements coming from specific equipment. This paper describes the global architecture of the XPOC system and gives examples of the analyses performed by some of the most important analysis modules. It explains the integration of the XPOC into the LHC control infrastructure along with its integration into the decision chain to allow proceeding with beam operation. Finally, it discusses the operational experience with the XPOC system acquired during the first years of LHC operation, and illustrates examples of internal system faults or abnormal beam dump executions which it has detected.
|
|
|
Poster WEPMU023 [1.768 MB]
|
|
|