A   B   C   D   E   F   G   H   I   J   K   L   M   N   O   P   Q   R   S   T   U   V   W   X   Y   Z  

Shirasawa, K.

Paper Title Page
THP085 Cooling System Design of Compact Klystron Modulator Power Supply in the XFEL Project at SPring-8 987
 
  • C. Kondo
    RIKEN Spring-8 Harima, Hyogo
  • T. Inagaki, T. Sakurai, T. Shintake, K. Shirasawa
    RIKEN/SPring-8, Hyogo
 
 

A klystron modulator power supply for XFEL project at SPring-8 has been developed, which concepts are a compact body, a low noise, and a good stability. The cooling system of the power supply is one of the most important key for the stable modulator. For example, temperature change of insulation oil in the tank caused drift of the klystron voltage, and higher oil temperature deteriorates insulation oil and electric components. We adopted simple and compact cooling systems utilizing natural conviction cooling, because of low costs, limited space, and maintenance free. In order to estimate the requisite cooling ability, we designed four types of cooling panels and measured the natural conviction heat transfer coefficient between the oil and each cooling panels. Using the results, we designed cooling systems composed of water cooling panels placed on the side walls and a water pipe hanged from the ceiling panel. The temperature of the inner oil of the power supply in the rated operation was suppressed below 43 degree C, which is agreed with our expectation. In this paper we present the design and ability of the power supply, and the key point of oil cooling.