WEPAB372 Design and Construction of Uninterruptible Paralleling Transfer Switches for an Emergency Power System in Taiwan Light Source 3581
 
  • Y.F. Chiu, W.S. Chan, K.C. Kuo, Y.-C. Lin
    NSRRC, Hsinchu, Taiwan
 
  The ATS of an emergency power system in Utility Building II has operated over 18 years; in recent years the failure rate is gradually increasing because of aged components. To improve old switches, schemes of upgrading and developing new and efficient transfer switches have been conducted cautiously. A new device named an Uninterruptible Paralleling Transfer Switch (UPTS) is designed and implemented to replace an existing ATS to enhance the performance to meet the requirements of uninterrupted power transfer. The UPTS can uninterruptedly switch the grid power to emergency power of a backup generator during a planned utility power outage, and also exactly switch emergency power to the grid power uninterruptedly when the utility power is restored. If grid power is unexpectedly lost, UPTS acts like a typical ATS, automatically transferring power from a primary source to a backup source with switching duration a few seconds. A practical UPTS has been assembled and installed in Utility Building II and has performed well effectively to eliminate power-switching transients.  
DOI • reference for this paper ※ https://doi.org/10.18429/JACoW-IPAC2021-WEPAB372  
About • paper received ※ 11 May 2021       paper accepted ※ 02 July 2021       issue date ※ 12 August 2021  
Export • reference for this paper using ※ BibTeX, ※ LaTeX, ※ Text/Word, ※ RIS, ※ EndNote (xml)  
 
WEPAB373 The Energy Management System in NSRRC 3585
 
  • C.S. Chen, W.S. Chan, Y.Y. Cheng, Y.F. Chiu, Y.-C. Chung, K.C. Kuo, M.T. Lee, Y.C. Lin, C.Y. Liu, Z.-D. Tsai
    NSRRC, Hsinchu, Taiwan
 
  Taiwan has been suffering from a shortage of natural resources for more than two decades. As stated by the Energy Statistics Handbook 2019 of Taiwan, up to 97.90% of energy supply was imported from abroad. This kind of energy consumption structure is fragile relatively. Not mention to the total domestic energy consumption annual growth rate is 1.97% in twenty years. Either the semiconductor or the integrated circuit-related industry is developed vigorously in Taiwan. All the facts cause us to face the energy problems squarely. Therefore, an energy management system (EnMS) was installed in NSRRC in 2019 to pursue more efficient energy use. With the advantages of the Archive Viewer - a utility supervisory control and data acquisition system in NSRRC, the data of energy use could be traced conveniently and widely. The model of energy use has been built to review periodically, furthermore, it provides us the accordance to replace the degraded equipment and alerts us if the failure occurs.  