Author: Chung, Y.-C.
Paper Title Page
WEPVA128 The Data Acquisition System and Inspection Equipment on Vibration Evaluation for Deionized and Cooling Water Pumps in TPS 3568
 
  • Y.-H. Liu, Y.-C. Chung, C.K. Kuan, Z.-D. Tsai
    NSRRC, Hsinchu, Taiwan
 
  The purpose of this paper is to evaluate the vibration amplitude and spectrum for TPS water pump systems. The utility systems operate continuously since 2014, some of deionized and cooling water pumps produced higher vibration amplitude and noise during operation. The possibly reason could be poor system accuracy, inappropriate installation and commission adjustment. The data acquisition system on vibration evaluation for deionizes water pumps was established in 2016. Accord-ing to the long-tern vibration amplitude recording, the system operational status could be clarified. After vibra-tion test for several months, the bearing of booster deion-ized water pump was found abrasive since coupling be-tween motor and pump misaligned. Besides, the founda-tion of copper deionized water pump system was broken and observed by rapidly increase vibration amplitude in short term. The water pump systems were repaired and maintained base on vibration evaluation. There is still some remain problems for deionized and cooling water pump systems. The utility systems could prevent mal-function through regular vibration inspection and daily data acquisition.  
DOI • reference for this paper ※ https://doi.org/10.18429/JACoW-IPAC2017-WEPVA128  
Export • reference for this paper using ※ BibTeX, ※ LaTeX, ※ Text/Word, ※ RIS, ※ EndNote (xml)