THPMW006 The Realization of the System for Rapid Detection of Bepc Ii Magnet Power Supply 3543
 
  • S.Y. Chen, M.C. Zhan, J.X. Zhang
    IHEP, Beijing, People's Republic of China
 
  To quickly find the causes of the accelerator unstable or lost beam caused by magnet power supply in the Beijing Electron Positron Collider running, this set of rapid detection system for magnet power supply is developed. The stability of the system in 8 hours is about 0.005%, it can acquire over nearly 500 sets of magnet power supply current value most quickly in the 0.33ms time. All data is written to the MySQL database in real time,So as to be able to quickly troubleshoot magnet power supply problem through historical data analysis of database comparison.  