Funding: Work supported by the U. S. Department of Energy Contract DE-AC02-76SF00515 Beam-based feedback control loops are required by the Linac Coherent Light Source (LCLS) program in order to provide fast, single-pulse stabilization of beam parameters. Eight transverse feedback loops, a 6x6 longitudinal feedback loop, and a loop to maintain the electron bunch charge were successfully commissioned for the LCLS, and have been maintaining stability of the LCLS electron beam at beam rates up to 120Hz. In order to run the feedback loops at beam rate, the feedback loops were implemented in EPICS IOCs with a dedicated ethernet multicast network. This paper will discuss the design, configuration and commissioning of the beam-based Fast Feedback System for LCLS. Topics include algorithms for 120Hz feedback, multicast network performance, actuator and sensor performance for single-pulse control and sensor readback, and feedback configuration and runtime control. |
||