JACoW logo

Joint Accelerator Conferences Website

The Joint Accelerator Conferences Website (JACoW) is an international collaboration that publishes the proceedings of accelerator conferences held around the world.


RIS citation export for TUPA16: Signal Processing for Beam Loss Monitor System at Jefferson Lab

TY  - CONF
AU  - Yan, J.
AU  - Allison, T.L.
AU  - Bruhwel, S.
AU  - Lu, W.
ED  - Schaa, Volker RW
TI  - Signal Processing for Beam Loss Monitor System at Jefferson Lab
J2  - Proc. of IBIC2018, Shanghai, China, 09-13 September 2018
CY  - Shanghai, China
T2  - International Beam Instrumentation Conference
T3  - 7
LA  - english
AB  - Ion Chamber and Photomultiplier Tube (PMT) were both used for beam loss monitor in the Machine Protection System (MPS) at Jefferson Lab. The requirements of signal processing of these detectors are different, so two VME-based signal processing boards, Beam Loss Monitor (BLM) board and Ion-Chamber board, were developed. The BLM board has fast response (< 1us) and 5 decades dynamic range from 10nA to 1 mA, while the Ion-Chamber board has 8 decades dynamic range from 100 pA to 10 mA and slower response. Both of boards provide functions of machine protection and beam diagnostics, and have features of fast shutdown (FSD) interface, beam sync interface, built-in-self-test, remotely controlled bias signals, and on-board memory buffer.
PB  - JACoW Publishing
CP  - Geneva, Switzerland
SP  - 245
EP  - 248
KW  - machine-protect
KW  - FPGA
KW  - controls
KW  - detector
KW  - operation
DA  - 2019/01
PY  - 2019
SN  - 978-3-95450-201-1
DO  - DOI: 10.18429/JACoW-IBIC2018-TUPA16
UR  - http://jacow.org/ibic2018/papers/tupa16.pdf
ER  -