A   B   C   D   E   F   G   H   I   J   K   L   M   N   O   P   Q   R   S   T   U   V   W   X   Y   Z    

Ke, M.

Paper Title Page
TUPLS136 Air Temperature Analysis and Improvement for the Technical Zone at TLS 1825
 
  • J.-C. Chang, J.-R. Chen, Z.-D. Tsai
    NSRRC, Hsinchu
  • M. Ke
    NTUT, Taipei
 
  This paper presents the air temperature analysis and control improvement for the technical zone, where many critical instrumentations of power supply, rf, vacuum and control apparatuses are located, at the Taiwan Light Source (TLS). The technical zone with circular shape is located on the core area of the storage ring. The diameter and height of the technical zone are 28.5m and 3m, respectively. Totally 13 temperature sensors are installed in this zone to online record the air temperature history. Because of insufficient cooling capacity and poor air circulation of the air-conditioning (A/C) system, the air temperature may reach to 30 degrees C, and spatial air temperature difference may be more than 7 degrees C. To cope with those problems, a computational fluid dynamics (CFD) code is applied to simulate the spatial temperature distribution. The A/C cooling capacity will be increased, and the air exit and exhaust distribution will be modified according to the simulated results.