Paper |
Title |
Page |
TUMPA06 |
RF Heat Load Compensation for the European XFEL |
348 |
|
- M.R. Clausen, T. Boeckmann, J. Branlard, J. Eschke, O. Korth, J. Penning, B. Schoeneburg
DESY, Hamburg, Germany
|
|
|
The European XFEL is a 3.4km long X-ray Free Electron Laser. The accelerating structure consists of 96 cryo modules running at 1.3 GHz with 10 Hz repetition rate. The injector adds two modules running at 1.3 and 3.9 GHz respectively. The cryo modules are operated at 2 Kelvin. Cold compressors (CCs) pump down the liquid Helium to 30 mbar which corresponds to 2 Kelvin. Stable conditions in the cryogenic system are mandatory for successful accelerator operations. Pressure fluctuations at 2 K may cause detuning of cavities and could result in unstable CC operations. The RF losses in the cavities may be compensated by reducing the heater power in the liquid Helium baths of the nine cryogenic strings. This requires a stable readout of the current RF settings. The detailed signals are read out from several severs in the accelerator control system and then computed in the cryogenic control system for heater compensation. This paper will describe the commissioning of the cryogenic control system, the communication between the control systems involved and first results of machine operations with the heat loss compensation in place.
|
|
|